Performance Level According To En 13849; Without Shutter; With Shutter - Domino F Series Product Manual

Hide thumbs Also See for F Series:
Table of Contents

Advertisement

Performance Level according to EN 13849

Without Shutter

• Without cross-wire short detection performance level d is reached.
• With cross-wire short detection performance level e is reached.
The functionality cross-wire short detection is activated on the Pilz safety
relay. Cross-wire short detection is switched off when using the setting "Cat
2/3". It is active when using the setting "Cat 4"
In systems without shutter the e-stop relay of the controller "PNOZ-S4" is
switching at every door opening. The replacement intervals of the e-stop
relay and guard door switch have to be defined according to the
application. The maximum cycle number of the guard door switch is often
shown in the data sheet. The maximum cycling number of the e-stop relay
is shown in
"Service: Replacement of Components" on page

With Shutter

For the system with shutter performance level d is reached.
According to the maximal cycle time of the shutter and guard door switch
the replacement intervals of both components have to be defined
according to the application. The maximum cycle number of the guard door
switch is often shown in the data sheet. The maximum cycling number of
the shutter can be found in
page
5-5.
EPT009665 Issue 2 May 2015
INSTALLATION INSTRUCTIONS
"Service: Replacement of Components" on
5-5.