7 Conditions
Rated Output
Current
Drive Model
2042
2056
2070
Table 7.10 Three-Phase 400 V Class (Finless-Type Drive)
Rated Output
Current
Drive Model
4001
4002
4004
4005
4007
4009
4012
4018
4023
4031
4038

Normal Duty Rating (ND)

Table 7.11 Single-Phase 200 V Class (Finless-Type Drive)
Rated Output
Current
Drive Model
B001
B002
28
Carrier
Frequency
(A)
(kHz)
33.0
8
47.0
8
60.0
8
Carrier
Frequency
(A)
(kHz)
1.2
8
1.8
8
3.4
8
4.8
8
5.6
8
7.3
8
9.2
8
14.8
8
18
8
24
8
31
8
Carrier
Frequency
(A)
(kHz)
1.2
2
1.9
2
YASKAWA TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Drive Watt Loss (W)
Heatsink Plate Loss
Interior Unit
Loss
73
108
171
Drive Watt Loss (W)
Heatsink Plate Loss
Interior Unit
Loss
9
11
15
18
18
25
32
52
92
75
108
Drive Watt Loss (W)
Heatsink Plate Loss
Interior Unit
Loss
8
14
Total
Loss
(P
)
Loss
212
285
347
455
455
626
Total
Loss
(P
)
Loss
11
20
16
27
31
46
42
60
49
67
65
90
85
117
149
201
207
299
240
315
319
427
Total
Loss
(P
)
Loss
6
14
11
25

Advertisement