YASKAWA CIPR-GA50UВ001AJ Series Installation & Primary Operation page 203

Finless-type ac drive, 200 v class, single-phase input: 1/6 to 3 hp, 200 v class, three-phase input: 1/6 to 25 hp, 400 v class, three-phase input: 1/2 to 25 hp
Table of Contents

Advertisement

Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2021
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2030
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2042
-, +1, +2
B1, B2
YASKAWA TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Recomm.
Applicable
Gauge
Gauge
AWG, kcmil
AWG, kcmil
8
14 - 8
10
14 - 8
8
14 - 8
14
14 - 10
8
14 - 8
8
12 - 6
8
12 - 6
6
12 - 6
12
12 - 8
8
10 - 6
6
12 - 6
6
12 - 6
4
10 - 2
10
14 - 6
6
10 - 6
17 UL Standards
Wire
Terminal
Stripping
Screw
*1
Length
Size and
mm
Shape
10
M4
10
M4
10
M4
10
M4
-
M4
10
M4
10
M4
10
M4
10
M4
-
M5
10
M4
10
M4
18
M5
10
M4
-
M5
Tightening
Torque
N∙m (lbf∙in)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.2 - 1.5
(10.6 - 13.3)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
2.0 - 2.5
(17.7 - 22.1)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
• AWG 8 ≤
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
2.0 - 2.5
(17.7 - 22.1)