17 UL Standards
Table 17.6 Required Short Circuit Protection for GA500 Finless-Type Drive: Three-
Semiconduc
tor Fuse
Part Number
Drive Model
Manufacturer:
Eaton/
Bussman
2001
FWH-25A14F
2002
FWH-25A14F
2004
FWH-25A14F
2006
FWH-25A14F
2008
FWH-70B
2010
FWH-70B
2012
FWH-70B
2018
FWH-90B
2021
FWH-90B
2030
FWH-100B
2042
FWH-150B
2056
FWH-200B
2070
FWH-200B
Table 17.7 Required Short Circuit Protection for GA500 Finless-Type Drive: Three-
Semiconduc
tor Fuse
Part Number
Drive Model
Manufacturer:
Eaton/
Bussman
4001
FWH-40B
4002
FWH-40B
4004
FWH-50B
4005
FWH-70B
4007
FWH-70B
210
Phase 200 V Class
Class CC, J or
T Fuse
Maximum
Amps
2
3.2
6
10
12
15
20
30
35
50
70
90
110
Phase 400 V Class
Class CC, J or
T Fuse
Maximum
Amps
2
3.5
7
9
12
YASKAWA TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
MCCB
Class RK5
(Schneider
Powerpact
Maximum
current
Amps
limiting MCCB)
HLL36015
HLL36015
HLL36015
HLL36015
HLL36015
HLL36015
HLL36020
HLL36035
HLL36040
-
-
-
-
MCCB
Class RK5
(Schneider
Powerpact
Maximum
current
Amps
limiting MCCB)
HLL36015
HLL36015
HLL36015
HLL36015
HLL36015
Enclosure
Fuse
Volume
Minimum (in
2
600
3.2
600
6
600
10
600
12
600
15
600
20
600
30
960
35
960
-
960
-
960
-
2560
-
2560
Enclosure
Fuse
Volume
Minimum (in
2
960
3.5
960
7
960
9
960
12
960
3
)
3
)