Code
Name
Parameter Selection
oPE08
Error
YASKAWA TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Causes
These parameters are set at the
same time:
• H3-02, H3-10, H7-30 = B
[PID Feedback]
• H6-01 = 1 [Terminal RP
Pulse Train Function = PID
Feedback Value]
These parameters are set at the
same time:
• H3-02, H3-10, H7-30 = C
[PID Setpoint]
• H6-01 = 2 [PID Setpoint
Value]
These parameters are set at the
same time:
• H3-02, H3-10, H7-30 = C
• b5-18 = 1 [PID Setpoint
Selection = Enabled]
These parameters are set at the
same time:
• H6-01 = 2
• b5-18 = 1
A function was set that is not
compatible with the control
method selected in A1-02
[Control Method Selection].
When A1-02 = 2 [OLV], you
used these parameter settings:
• n2-02 > n2-03 [Automatic
Freq Regulator Time 1 >
Automatic Freq Regulator
Time 2]
• C4-02 > C4-06 [Torque
Compensation Delay Time >
Motor 2 Torque Comp Delay
Time]
15 Troubleshooting
Possible Solutions
Remove the function settings that are not
in use.
1.
Push ENTER Key to show U1-18
[oPE Fault Parameter], and find
parameters that are not in the
applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the
same time, other oPExx errors have
priority over oPE02.
• Set n2-02 < n2-03.
• Set C4-02 < C4-06.
159