Code
Name
Multi-Function Input
oPE03
Setting Err
YASKAWA TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Causes
The settings for these
parameters do not agree:
• H1-01 to H1-07 [Terminals
S1 to S8 Function Selection]
• H7-01 to H7-04 [Virtual
Multi-Function Inputs 1 to 4]
The settings for MFDIs overlap.
Note:
This does not include H1-xx
= 20 to 2F [MFDI Function
Select = External Fault]
and [Reserved].
You did not set these pairs of
MFDI functions to Digital
Inputs (H1-xx and H7-01 to H7-
04) at the same time:
• Setting values 10 [Up
Command] and 11 [Down
Command]
• Setting values 75 [Up 2
Command] and 76 [Down 2
Command]
• Setting values 42 [Run
Command (2-Wire Sequence
2)] and 43 [FWD/REV (2-
Wire Sequence 2)]
You set a minimum of two of
these MFDI combinations to
Digital Inputs (H1-xx and H7-01
to H7-04) at the same time:
• Setting values 10 [Up
Command] and 11 [Down
Command]
• Setting values 75 [Up 2
Command] and 76 [Down 2
Command]
• Setting value A [Accel/Decel
Ramp Hold]
• Setting value 1E [Reference
Sample Hold]
• Setting values 44 to 46 [Add
Offset Frequency 1 to 3 (d7-
01 to d7-03)]
15 Troubleshooting
Possible Solutions
Correct the parameter settings.
Set the parameters correctly to prevent
MFDI function overlap.
Set the MFDI pairs.
Remove the function settings that are not
in use.
155