YASKAWA CIPR-GA50UВ001AJ Series Installation & Primary Operation page 164

Finless-type ac drive, 200 v class, single-phase input: 1/6 to 3 hp, 200 v class, three-phase input: 1/6 to 25 hp, 400 v class, three-phase input: 1/2 to 25 hp
Table of Contents

Advertisement

15 Troubleshooting
Code
Name
Excessive Rated
End1
Voltage Setting
Iron Core Saturation
End2
Coefficient
Rated Current Setting
End3
Alarm
Adjusted Slip
End4
Calculation Error
Resistance Tuning
End5
Error
Leakage Inductance
End6
Alarm
164
Causes
The torque reference was more
than 20% during Auto-Tuning
or the no-load current that was
measured after Auto-Tuning is
more than 80%.
The motor nameplate data
entered during Auto-Tuning is
incorrect.
Auto-Tuning results were not in
the applicable parameter setting
range, and E2-07 or E2-08
[Motor Saturation Coefficient
2] have temporary values.
The rated current value is
incorrect.
The Auto-Tuning results were
not in the applicable parameter
setting range.
The motor rated slip that was
measured after Stationary Auto-
Tuning was 0.2 Hz or lower.
The motor rated slip that was
measured after compensation
with E2-08 [Motor Saturation
Coefficient 2] is not in the
applicable range.
The secondary resistor
measurement results were not in
the applicable range.
The Auto-Tuning results of the
Line-to-Line Resistance were
not in the applicable range.
The Auto-Tuning results were
not in the applicable parameter
setting range.
YASKAWA TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Possible Solutions
• Make sure that the input motor
nameplate data is correct.
• Do Auto-Tuning again and correctly
set the motor nameplate data.
• If you can uncouple the motor and
load, remove the motor from the
machine and do Rotational Auto-
Tuning again.
• If you cannot uncouple the motor and
load, use the results from Auto-
Tuning.
• Make sure that the input motor
nameplate data is correct.
• Do Auto-Tuning again and correctly
set the motor nameplate data.
• Examine and repair damaged motor
wiring.
• If you can uncouple the motor and
load, remove the motor from the
machine and do Rotational Auto-
Tuning again.
Do Auto-Tuning again and set the correct
rated current shown on the motor
nameplate.
• Make sure the input motor nameplate
data is correct.
• Do Rotational Auto-Tuning again and
correctly set the motor nameplate
data.
• If you cannot uncouple the motor and
load, do Stationary Auto-Tuning 2.
• Make sure that the input motor
nameplate data is correct.
• Examine and repair damaged motor
wiring.
Make sure that the input motor
nameplate data is correct, and do Auto-
Tuning again.