In case of Konfort 760R, 760R Bus and 780R BiGas units, ensure that
the quick connector of the oil bottle will not be obstructed:
on the oil injection bottle will not be obstructed
In case that the connector would be obstructed, replace the entire top
part of the bottle.
Check the path of the silicone tube which connects the bottle to the
manifold of the equipment (see Image 7.26), and verify its integrity.
Ensure that the EVIO solenoid valve, responsible of the oil injection,
will work properly, by manually activating it from the Power outputs
menu.
In case of Konfort 705R, 710R or 720R units, ensure that the oil
bottle will
be fully connected. If necessary, replace the quick
connector of the bottle itself.
7.7

The unit does not inject UV additive

Check that the UV quantity inside the bottle will be sufficient.
In case of Konfort 705R, 710R or 720R units, check that the liquid
outlet of the bottle will be present and that it will be immersed into
the UV additive.
In case of Konfort 705R, 710R or 720R units, ensure that the liquid
outlet of the UV bottle will not be obstructed.
Copyright © 2014 – TEXA S.p.A.
Image 7.30 – Check that the quick connector
142
TEXA Technical Assistance