Monitoring via the Web Browser

12.1

Alarms

This selection provides the status of the base alarms by indicating if an alarm has been triggered. Under
the State column, the status will appear in red if an alarm has been activated. The status will be
displayed in green when the alarm condition is not present.
Fig. 12.1 Click on Alarms in the Monitor menu to see if any base alarms have been triggered.
ID
Description
State
Total Time in Alarm
State
Basic Alarm Monitoring
Alarm ID number.
User-definable description for the discrete alarm point.
The current state of the alarm. (Clear or Alarm)
Counter for the total time the point has been in the alarm state.
1) This timer is always on.
2) The maximum time value is 18 hours. Once 18 hours is reached, the
timer will stop counting.
3) The timer will survive a soft reboot (a reboot from the web interface).
4) The timer will not survive a hard reboot (losing power, disconnection, etc).
The timer will be restored to its previously saved value.