Counter Inputs; Analog Inputs; Digital Outputs; Data And Event Logger - WAGO -TO-PASS 761 Manual

Telecontrol module for fault detection/indication, position monitoring and remote control to-pass mobile, 4 ai, web, modbus
Hide thumbs Also See for WAGO-TO-PASS 761:
Table of Contents

Advertisement

WAGO-TO-PASS® 761
761-316 TO-PASS® Mobile, 4 AI, Web, MODBUS
3.6.8

Counter Inputs

Table 21: Technical Data Counter Inputs

No. of counters
Counter frequency
Resolution
Count direction
3.6.9

Analog Inputs

Table 22: Technical Data Analog Inputs

Number of inputs
Input current
Internal resistance
Resolution
Measuring error (25°C)
Temperature coefficient
3.6.10

Digital Outputs

Table 23: Technical Data Digital Outputs

Number of outputs
Output type
Output current
Type of load
Energy dissipation W
(unique switching off)
3.6.11

Data and Event Logger

Table 24: Technical Data Data and event logger

Memory type
Memory size
Manual
Version 2.0.0
max.
Without configured
counters
With configured
counters
Device Description
Max. 4, configurable
Max. 2000 Hz
32 bits
Up/Down
4
0/4 mA ... 20 mA
Approx.. 200 Ω / 20 mA
12 bit
< ±1 % of the full scale value
< ±0.1 % / K of the full scale value
2
Semiconductor outputs
0.5 A/30 V DC
Resistive, inductive, lamps
125 mJ;
2
L
= 2 * W
/ I
max
max
Ring memory
2048 process images
1024 process images
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

761-316

Table of Contents