Multiplex Input - WAGO -TO-PASS 761 Manual

Telecontrol module for fault detection/indication, position monitoring and remote control to-pass mobile, 4 ai, web, modbus
Hide thumbs Also See for WAGO-TO-PASS 761:
Table of Contents

Advertisement

60
Parameterizing
7.5.2

Multiplex Input

You can configure digital inputs DI1 ... DI4 as multiplex inputs. These four inputs
will then additionally be read in as a combination and intepreted as a binary
number. The following applies in this case:
DI1 = 2
DI2 = 2
DI3 = 2
DI4 = 2
Thus, for example, if DI1 and DI3 are set, then the binary number is 5. If only DI4
is set, then the binary number is 8.
In the multiplex table you can define an alarm message for each of the 16 statuses
(0 ... 15). The recipients of the messages can be selected using the multiplex
settings.
Counter inputs cannot be evaluated as multiplex inputs!
Counter inputs cannot be evaluated as multiplex inputs, as these inputs cannot be
set.
0
= 1,
1
= 2,
2
= 4 and
3
= 8.
761-316 TO-PASS® Mobile, 4 AI, Web, MODBUS
WAGO-TO-PASS® 761
Manual
Version 2.0.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

761-316

Table of Contents