Factory Settings - Bender ISOMETER iso1685D Series Manual

Insulation monitoring device for unearthed ac, ac/dc and dc power supplies it systems up to ac 1000 v/dc 1500 v or ac 200 v/dc 3000 v
Table of Contents

Advertisement

Settings

9.2 Factory settings

Response values, alarms and profile
Parameter
Measurement method
Insulation response value R
an1
Insulation response value R
an2
Fault memory
Coupling monitoring
Switching elements
Parameter
Relay 1 (11/12/14)
Relay 2 (21/22/24)
Relay 3 (31/32/34)
Insulation fault location (only iso1685DP)
Parameter
EDS mode
PGH current
36
Value
Status
Power circuits
40kΩ
10kΩ
off
on
Value
Status
Operating mode: N/C operation
Function: Insulation measurement
Operating mode: N/C operation
Function: Insulation measurement
Operating mode: N/C operation
Function: Device error
Value
Status
auto
25 mA
Settings
BMS
Parameter
BMS address
BMS termination
Digital inputs
Parameter
Digital input 1
Digital input 2
Other
Parameter
Standby mode (disconnection from the
mains)
Permissible system leakage capacitance
Buzzer
Menu language
Password query
Password
Value
Status
2
ON
Value
Status
Mode (operating mode): active high
Function: Test
Mode (operating mode): active high
Function: standby
Value
Status
off
depending on the set measurement method
(refer to
"12. Device
profiles")
off
German
off
0000
iso1685DP_D00272_03_M_XXEN/08.2017