Werkseinstellungen
Ansprechwerte
Ansprechwert R
(Alarm 1) ..................................................................40 kΩ
an1
Ansprechwert R
(Alarm 2) ..................................................................10 kΩ
an2
Fehlerspeicher............................................................................................aus
Ankoppelüberwachung .............................................................................. ein
Geräteprofil ..........................................................................„Leistungskreise"
Art des zu überwachenden Netzes
Netzform ...................................................................................................3AC
Zeitverhalten
Anlaufverzögerung t
.............................................................................0 s
Anlauf
Schaltglieder
Relais 1
Arbeitsweise ........................................................................ Ruhestrom (N/C)
Funktion 1 .................................................................................... Iso. Alarm 1
Funktion 2 ..................................................................................................aus
Funktion 3 .............................................................................. Anschlussfehler
Relais 2
Arbeitsweise ........................................................................ Ruhestrom (N/C)
Funktion 1 .................................................................................... Iso. Alarm 2
Funktion 2 ................................................................................... Gerätefehler
Funktion 3 .............................................................................. Anschlussfehler
Schnittstellen
IP-Adresse ...................................................................... manuell 192.168.0.5
Netzmaske ............................................................................... 255.255.255.0
Geräteadresse BS-Bus ................................................................................... 1
Sonstiges
Sprache .............................................................................................. Deutsch
Inbetriebnahmeassistent ............................................................................ an
Technische Daten
Isolationskoordination (IEC 60664-1/IEC 60664-3)
Bemessungsspannung ........................................................................ 1000 V
Überspannungskategorie (OVC) ..................................................................III
Bemessungs-Stoßspannung (IEC 60664-1) .............................................. 8 kV
Bemessungsisolationsspannung (IEC 60664-1) ................................... 1000 V
Spannungsprüfung, Stückprüfung (IEC 61010-1) ............................ AC 2,2 kV
Versorgungsspannung
Versorgung über A1/+,A2/-:
Versorgungsspannungsbereich U
Toleranz von U
.................................................................. -30...+15 %
S
Frequenzbereich von U
.................................................DC, 50...400 Hz
s
Überwachtes IT-System
Netznennspannungsbereich U
Schaltvermögen interne Netztrennschalter ......AC 0...690 V, DC 0...1000 V
....................................................... AC/DC 0...600 V (für UL Anwendungen)
Ansprechwerte
Ansprechwert R
(Alarm 1) .................................................... 1 kΩ...10 MΩ
an1
Ansprechwert R
(Alarm 2) ................................................... 1 kΩ...10 MΩ
an2
.............................. AC/DC 24...240 V
s
.............................................................offline
n
Factory settings
Response values
Response value R
(Alarm 1) ................................................................40 kΩ
an1
Response value R
(Alarm 2) ................................................................10 kΩ
an2
Fault memory .............................................................................................off
Coupling monitoring ...................................................................................on
Device profile ........................................................................."Power circuits"
Type of system to be monitored
System type ..............................................................................................3AC
Time response
Start-up delay t
......................................................................................0 s
Start
Switching elements
Relay 1
Operating principle ...................................................................N/C operation
Function 1 .................................................................................... Ins. Alarm 1
Function 2 ..................................................................................................aus
Function 3 .............................................................................Connection fault
Relay 2
Operating principle ...................................................................N/C operation
Function 1 .................................................................................... Ins. Alarm 1
Function 2 .................................................................................... Device fault
Function 3 .............................................................................Connection fault
Interfaces
IP adress.......................................................................... manual 192.168.0.5
Network mask .......................................................................... 255.255.255.0
Adress BS bus ................................................................................................ 1
Other
Language ............................................................................................German
Commissioning wizard ................................................................................on
Technical data
Insulation co-ordination (IEC 60664-1/IEC 60664-3)
Rated voltge ........................................................................................ 1000 V
Overvoltage category (OVC) .........................................................................III
Rated impulse voltage (IEC 60664-1) ...................................................... 8 kV
Rated insulation voltage (IEC 60664-1) ............................................... 1000 V
Voltage test, routine test (IEC 61010-1) .......................................... AC 2.2 kV
Supply voltage
Supply via A1/+,A2/-:
Supply voltage range U
.............................................. AC/DC 24...240 V
s
Tolerance of U
.................................................................... -30...+15%
s
Frequency range of U
....................................................DC, 50...400 Hz
s
IT system being monitored
Nominal system voltage range U
Circuit capacity internal mains switch ...............AC 0...690 V, DC 0...1000 V
....................................................... AC/DC 0...600 V (für UL Anwendungen)
Response values
Response value R
(Alarm 1) .................................................. 1 kΩ...10 MΩ
an1
Response value Ran2 (Alarm 2) ............................................... 1 kΩ...10 MΩ