Communications Wiring; Protocol Overview - Carrier Fan Coil Integration Manual

Table of Contents

Advertisement

Communications wiring

Communications wiring

Protocol Overview

You can set the Fan Coil to communicate 1 of 4 different protocols:
BACnet MS/TP (page 5)
BACnet ARC156 (page 9)
N2 (page 13)
Modbus (page 11)
LonWorks (page 15)
The default setting is BACnet MS/TP. You set the protocol and baud rate on the Comm Selector DIP switches on
the controller. See table below for specific switch settings.
The third party connects to the controller through the Comm port for BACnet MS/TP, N2, Modbus, and through the
Option Card port for the LonWorks Option Card.
NOTES
Changing protocol requires no programming or point assignment by the installer or operator.
Power must be cycled after changing the Comm Selector DIP switches or connecting the LonWorks Option
Card.
Comm Selector DIP switch settings for protocols and baud
Protocol
BACnet MS/TP
(Default)
BACnet ARC156
1
N2
Modbus
LonWorks
2
1
N2
must have 9600 bps baud
2
LonWorks
must have 38.4 kbps baud
Baud Rate
9,600 bps
19.2 kbps
38.4 kbps
76.8 kbps
(Default)
Fan Coil
Integration Guide
Baud Rate
3
4
1
Off
Off
Select Baud
Off
Off
N/A
On
Off
Off
Off
On
Select Baud
On
On
On
1
2
Off
Off
Off
On
On
Off
On
On
2
Select Baud
N/A
Off
Select Baud
Off
4
CARRIER CORPORATION ©2020
All rights reserved