Write And Read Access Via Fc 3 And Fc 6 - Siemens SINAMICS G120 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Modbus
Description
Reg.
No.
Technology controller adjustment
40510
Time constant for actual value filter of
the technology controller
40511
Scaling factor for actual value of the
technology controller
40512
Proportional amplification of the
technology controller
40513
Integral time of the technology
controller
40514
Time constant D-component of the
technology controller
40515
Max. limit of technology controller
40516
Min. limit technology controller
PID diagnostics
40520
Effective setpoint acc. to internal
technology controller MOP ramp-
function generator
40521
Actual value of technology controller
after filter
40522
Output signal technology controller
6.2.3.5

Write and read access via FC 3 and FC 6

Function codes used
For data exchange between the master and slave, predefined function codes are used for
communication via Modbus.
The Control Unit uses the Modbus function code 03, FC 03, (read holding registers) for
reading and the Modbus function code 06, FC 06, (preset single register) for writing.
Structure of a read request via Modbus function code 03 (FC 03)
All valid register addresses are permitted as a start address. If a register address is invalid,
exception code 02 (invalid data address) is returned. An attempt to read a write-only register
or a reserved register is replied to with a normal telegram in which all values are set to 0.
Using FC 03, it is possible to address more than 1 register with one request. The number of
addressed registers is contained in bytes 4 and 5 of the read request.
Number of registers
If more than 125 registers are addressed, exception code 03 (Illegal data value) is returned.
If the start address plus the number of registers for an address are outside of a defined
register block, exception code 02 (invalid data address) is returned.
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
Modbus
Unit
Scaling
access
factor
R/W
--
100
R/W
%
100
R/W
--
1000
R/W
s
1
R/W
--
1
R/W
%
100
R/W
%
100
R
%
100
R
%
100
R
%
100
Configuring the fieldbus
6.2 Communication via RS485
On/Off text
Data / parameter
or value range
0.00 ... 60.0
p2265
0.00 ... 500.00
p2269
0.000 ... 65.000 p2280
0 ... 60
p2285
0 ... 60
p2274
-200.0 ... 200.0 p2291
-200.0 ... 200.0 p2292
-100.0 ... 100.0 r2250
-100.0 ... 100.0 r2266
-100.0 ... 100.0 r2294
143