Ann-Sec Enable - Honeywell NOTIFIER SFP-10UD Series Manual

Fire alarm control panels
Hide thumbs Also See for NOTIFIER SFP-10UD Series:
Table of Contents

Advertisement

Programming
This screen shows the Input Zone that has been assigned to be the All-Call Zone. In this example,
Zone 1 is the All-Call Zone. The All-Call Zone can be changed by pressing the 1 key while view-
ing the ANN-AUDIO Options Screen. The following screens will be displayed.
These screens allow the programmer to select which Input Zone will be assigned as the All-Call
Zone.

ANN-SEC Enable

The ANN-SEC option must be enabled if any modules are connected to the ANN-SEC option card
at J13. To enable the Secondary ANN-BUS, press 2 while viewing ANN-BUS Screen #3 so that the
display reads ANN-SEC ENABLE YES. Each press of the 2 key will cause the display to toggle
between ANN-SEC ENABLE YES and ANN-SEC ENABLE NO. The factory default setting is ANN-
SEC ENABLE NO.
88
ANN-AUDIO ALL CALL
1=NO ALL CALL ZONE
2=INPUT ZONE 1
3=INPUT ZONE 2
All-Call Options Screen #1
ANN-AUDIO ALL CALL
1=INPUT ZONE 3
2=INPUT ZONE 4
3=INPUT ZONE 5
All-Call Options Screen #2
ANN-AUDIO ALL CALL
1=INPUT ZONE 6
2=INPUT ZONE 7
3=INPUT ZONE 8
All-Call Options Screen #3
(SFP-10UD Only)
ANN-AUDIO ALL CALL
1=INPUT ZONE 9
2=INPUT ZONE 10
All-Call Options Screen #4
(SFP-10UD Only)
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
Master Programming Level