N-ANN-LED Annunciator Installation for Canadian Applications
To Remote Station Receiver
ALARM
TROUBLE
SUPERVISORY
Figure F.2 Alternate Transmission for Alarm, Trouble, and Supervisory Signals
Notes:
1.
Relays 1 and 2 on the N-ANN-RLY must be programmed for latching alarm activation.
2.
Relays 3 and 4 on the N-ANN-RLY must be programmed for non-latching trouble activation.
3.
Relays 5 and 6 on the N-ANN-RLY must be programmed for supervisory activation with
latching/non-latching set in accordance with the local AHJ.
4.
The N-ANN-RLY must be mounted inside the FACP cabinet.
5.
Refer to the N-ANN-RLY Document #53318 for installation instructions.
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C1 2/24/2011
C
+
NC
NO
-
C
NC
NO
C
NC
+
NO
-
C
NC
NO
C
+
NC
NO
-
C
NC
NO
Relay 1
TB2
Relay 2
TB2
Relay 3
TB4
Relay 4
TB4
Relay 5
TB5
Relay 6
TB5
N-ANN-RLY
-
+
Canadian Application
TB9
2
Non-resettable
1
Aux Power
FACP
157