NFPA Standard-Specific Requirements
NFPA 72 Proprietary Protective Signaling Systems
Fire Alarm Control Panel
FACP Main Board
Form-C Alarm contact programmed to
activate on General Alarm.
Form-C Trouble contact which will
automatically activate on any Trouble
condition.
Form-C relay contact programmed to
activate on Supervisory condition.
Notes:
1.
Connection between the SFP-5UD/SFP-10UD
and the transmitter are supervised by the
transmitter.
2.
This SFP-5UD/SFP-10UD Transmitter
arrangement can be employed for NFPA 72
Proprietary Protective Signaling System.
3.
Potter Electric Model EFT-C has not been
tested for UL 864 9th Edition and is for use in
retrofit applications only.
150
Figure B.4 Proprietary Protective Signaling System
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012