ANN-BUS Devices
2.
Connect the N-ANN-S/PG to the FACP as illustrated in Figure 2.23.
Primary ANN-BUS
SFP-5UD/SFP-10UD
ANN-BUS and power wiring are
supervised and power-limited
3.
Using the DIP switches on the back of the N-ANN-S/PG module, assign an ID number
(address) to the module.
4.
Select the address and configuration options for the N-ANN-S/PG module as described in the
Programming section of this manual (refer to"ANN-BUS" on page 82).
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to"Auto-Configure" on page 83).
5.
Connect a printer to the N-ANN-S/PG Parallel and/or Serial connectors (refer to Figure 2.23
on page 49).

Specifications

Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6"W x 7-3/4"H x 1-7/16"D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
PRN-6 Printer Installation
When connected to the FACP via the N-ANN-S/PG module, the PRN-6 prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the event
occurred. It provides 80 columns of data on standard 9" x 11" tractor-feed paper. This section con-
tains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6 Printer
Remote printers require a primary AC power source. If required for the fire alarm system configu-
ration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power
source (battery backup). Since a secondary power source is not provided as a standard feature, a
separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of NFPA 72.
Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the N-ANN-S/PG module using a standard DB-25
cable. One end of the cable will plug into the DB-25 connector on the PRN-6 printer and the other
end plugs into the parallel connector on the N-ANN-S/PG module. Note that the 9-pin DB-9 port
on the N-ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics
parallel printer cable. Connect either a serial or parallel printer, but not both at the same time.
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
TB3
Primary ANN-BUS
Figure 2.23 N-ANN-S/PG Connection to FACP
o
F to 120
o
N-ANN-S/PG Module
F (0
o
C to 49
o
C)
Installation
Parallel
Cable
Connectors
for connection
to printer
Serial
49