System Operation
9.2.3 Using the Menus
To move through the menus:
To select an option:
Exit Menu

9.3 Basic Operation

9.3.1 Setting Time and Date
NOTE: The panel's time is as accurate as the input AC power line frequency and may drift over time if the frequency fluctuates.
1.
Select 4 for Set Date & Time.
2.
Make changes in the fields on the screen. Use right arrow to move through the fields. Use the up or down arrow key to select options in
the fields.
3.
When the date and time are correct, press ENTER.
9.3.2 Disable / Enable a Point
1.
Select 2 for Point Functions.
2.
Select 1 for Disable/Enable Point.
Disable / Enable NACs by Template
1.
Press 1 for Disable NACs by Template, or press 2 to Enable NACs by Template.
2.
Use the up or down arrow key to move through the list of templates. Press ENTER to select the current template.
Disable / Enable NACs by Group
1.
Press 3 to Disable NACs by Group, or press 4 to Enable NACs by Group.
2.
Use the up or down arrow key to move through the list of groups. Press ENTER to select the group highlighted.
Disable / Enable Zone Points
1.
Press 5 to Disable Zone Points, or press 6 to Enable Zone Points.
2.
Use the up or down arrow key to move through the list of zones. Press ENTER to select the zone highlighted.
Disable / Enable Point
1.
Press 7 to Disable /Enable Point.
2.
Choose module.
3.
Use the up or down arrow key to choose point and press ENTER.
4.
Press right arrow to disable or enable point.
Inhibit Output Group
Inhibiting an output group prevents the group from being utilized by system mapping. While inhibited, no event in the system can activate
the output group.
1.
Press 8 to inhibit output group.
2.
Use the up or down arrow key to select the group to be inhibited.
3.
Press right arrow to inhibit the group.
4.
Press right arrow again to enable the group.
9.3.3 View Event History
Use the View Event History feature to display events on LCD. From the Main Menu, press 3 to select Event History. Events will begin dis-
playing with most recent events first.
The panel can store up to 1000 events. When it reaches its 1000-event capacity, it will delete the oldest events to make room for the new
events as they occur. In networked setups, each panel stores up to 1000 of its own events. When using the HFSS Software Suite, all 1000
events from every panel in the network will be uploaded.
On multi-site displays, pressing ENTER or right arrow brings you directly into View Event History and allows you to view the Event History
from every panel in each of the sites that the multi-site display is assigned to.
To clear the event history
From the Installer menu select 1 for System Tests. From the test menu select 6 Clear History Buffer.
Single Key Acknowledge
This feature allows the user to press the ACK and display the oldest un-acknowledged event in the system. Pressing ACK again will
acknowledge the event, then display the next oldest un-acknowledged event without pressing the arrow keys.
114
Use the up and down arrow key to move the cursor through the options in a menu. Use the left arrow
key to move to a previous menu.
Enter the number of the option, or press ENTER if the option has the = symbol next to it.
Press the left arrow.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022