Product Description
The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP with the FLPS-3 power supply. This applies
to the SFP-5UD and SFP-5UDE.
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
Primary
ANN-BUS
ANN-SEC
Option Card
Remote
Synchronization
Output
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability with FACP and FLPS-3 Power Supply
18
TB9
0.5 amp max
per circuit
0.5 amp max
per circuit
TB5
2.5 amps max
per circuit
2.5 amps max
per circuit
TB7
2.5 amps max
per circuit
2.5 amps max
per circuit
TB3
0.5 amp max
per circuit
TB1
0.5 amp max
per circuit
TB2
0.040 amp max
per circuit
Standby
1.0 amp max
per panel
Standby
1.0 amp max
per panel
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
Specifications
Alarm
3.0 amps
max
per panel