Master Programming Level
3.5.4 System Setup
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
NOTE: A relay programmed with the Silenceable Alarm type will deactivate when the FACP
Alarm Silenced LED is illuminated.
System Setup allows the programmer to configure the following control panel features:
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout, which is blank, to a user defined readout when the control panel is in
Normal condition
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. If the Trouble
Reminder feature is not enabled and a trouble condition is not cleared within 24 hours, the
panel will reactivate the trouble sounder and retransmit the trouble condition to the central
station if connected
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to "Canadian Option" on page 81).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
Charger Disable: This option allows the programmer to disable the onboard battery charger in
the event an external battery charger is being used
Pressing 1 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
1=TIMERS
2=BANNER
3=TIME-DATE
1=TROUBLE REMIND
2=CANADIAN OPTION OFF
3=CHARGR DISABLE
SYSTEM SETUP
System Setup Screen #1
SYSTEM SETUP
System Setup Screen #2
Programming
NO
NO
75