Trouble Operation

4.4 Trouble Operation
With no alarms in the system, the detection of a trouble will cause the following:
The piezo to pulse 1 second On and 1 second Off
The system Trouble LED to flash one second On and one second Off
The trouble relay to activate
TROUBL with device type, adjective/noun, address and trouble description will appear on the
LCD display
The same message, along with the time and date, is sent to the optional printer and the history
buffer.
Communicate the trouble conditions to the Central Station
Terminate upload or download communications
Note that specific troubles will initiate additional actions; for example, loss of AC power will turn
off the AC Power LED, etc.
Input Zone
For Input Zones, the following is a typical message that could appear on the LCD display for a
device trouble:
The information displayed in the above example provides the following information:
First line in display:
– The type of event; in this example OPEN indicating a circuit trouble
– Device type identifier; in this example, PULL STATION indicates a manual device. Other
device type identifiers which can be displayed include SMOKE for Smoke Detector, HEAT
for Heat Detector, etc.
Second line in display:
– <ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
– <NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
Third line in display indicates Zone and the fault condition. Other possible troubles include:
OPEN - indicating an open circuit
DIRTY - maintenance alert indicating that an i
limit and is in need of maintenance before the performance is compromised
Fourth line in display:
– Time; the current time in this example is 10:00A which represents 10:00 AM
– Date; the current month, day and year in this example is 11 for November, 10 for the 10th
day of the month and 09 for the year 2009
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
TROUBL PULL STATION
<ADJ> <NOUN>
ZONE 10 OPEN FAULT
10:00A 111009
Operating Instructions