Section 3: Programming; User Programming - Honeywell NOTIFIER SFP-10UD Series Manual

Fire alarm control panels
Hide thumbs Also See for NOTIFIER SFP-10UD Series:
Table of Contents

Advertisement

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to
Program feature or
Permitted in UL
option
864? (Y/N)
Trouble Call Limit
Remote Download
Combo
Combo
w/AutoResettable
Superv

3.1 User Programming

The SFP-5UD/SFP-10UD FACP is completely field programmable using the panel keypad and
requires no special software skills.
CAUTION:
!
WHILE PROGRAMMING THE FACP, THE FIRE PROTECTION CAPABILITIES OF THE CONTROL
PANEL ARE ENABLED. PROGRAMMING MODE TIMES-OUT AFTER 10 MINUTES OF
INACTIVITY.
Site-specific programming may be accomplished in the following ways:
Manual programming or editing, using the FACP keypad
Remote Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and modem. For programs requiring a large
amount of data entry, this method may be preferred. A PK-CD programming CD ROM can be
ordered for this purpose
Local Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and USB connection. For programs requiring a
large amount of data entry, this method may be preferred. A PK-CD programming CD ROM
can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012

Section 3: Programming

specific values or not used at all as indicated below:
N
Refer to "Trouble Call Limit (Dialer Runaway Prevention)" on
Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble
to from 1 to 99 within a 24 hour period
Y
Refer to"Remote Download" on page 132.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Y
Refer to Table 3.1 on page 64.
Y
Refer to Table 3.1 on page 64.
FIRE PROTECTION ENABLED
SYSTEM ALL NORMAL
10:00A 070707
Possible settings
page 100.
Settings permitted in
UL 864
Trouble Call Limit = 0
for unlimited Central
Station trouble calls
Remote Download
Proprietary Yes for
Proprietary system
intended to protect only
contiguous properties
One Waterflow and one
Supervisory device
One Waterflow and one
Supervisory device
58