Ann-Rly Options Screen; Ann-Sec Enable - Honeywell GF505 Manual

Fire alarm control panels
Table of Contents

Advertisement

Programming
The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed GFANN-80 module will ever
sound. Pressing 1 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo
Enable No.
The Lock Enable option allows the programmer to select whether or not the GFANN-80 annunciator must be unlocked by its key before
any annunciator key presses will function. Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select whether the Ack/Step button on any
installed GFANN-80 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1
causes the display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step button
never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the Silence button on any installed
GFANN-80 annunciator will function normally or always be ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes
the display to toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never func-
tions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the Reset button on any installed
GFANN-80 annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes
the display to toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never func-
tions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the Drill button on any installed GFANN-
80 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display
to toggle between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never functions).

ANN-RLY Options Screen

PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
The GFANN-RLY module provides ten Form-C relays which can be programmed for various functions. The initial screen displays
Relays 1 through 3. Pressing the down arrow key will display the remaining relays for this module.
To program any of the GFANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key correspond-
ing to the relay to be programmed. Following is a list of the available programming options for each relay:
General Alarm
General Trouble
General Supervisory
AC Loss
Waterflow Delay
Input Zone 1
Input Zone 2
Input Zone 3
Input Zone 4
Input Zone 5
Input Zone 6
Input Zone 7
Input Zone 8
Input Zone 9
Input Zone 10
Silenceable Alarm
Not Assigned

ANN-SEC Enable

The ANN-SEC option must be enabled if any modules are connected to the ANN-SEC option card at J13. To enable the Secondary
ANN-BUS, press 2 while viewing ANN-BUS Screen #3 so that the display reads ANN-SEC ENABLE YES. Each press of the 2 key will
cause the display to toggle between ANN-SEC ENABLE YES and ANN-SEC ENABLE NO. The factory default setting is ANN-SEC
ENABLE NO.
64
Pressing 3 for ANN-RLY Options while viewing ANN-BUS Screen #2 will cause the following screen to be
displayed:
ANN-RLY OPTIONS
1=RELAY 1
2=RELAY 2
3=RELAY 3
ANN-RLY Options Screen
IN ZONE 1
IN ZONE 2
IN ZONE 3
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Master Programming Level