Programming
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR T TIME
Primary/Secondary Screen #1
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
92
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be dis-
played:
RANGE 0000-FFFF
The Account Code, which is assigned by a Central Station, depends on the communication format
being used. The Account Code screen will have a flashing cursor in the lower left corner. Program
the supplied 4-digit account code using 0 - 9 and A - F keys. Enter the first digit, then press the
right arrow key to move the cursor to the right, one position. Repeat the process until all digits are
entered.
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be dis-
played:
ENTR USING 24HR TIME
RANGE 0000-2359
Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour
Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen.
Enter a four digit number representing the test time using military time (0000 = midnight and 2359
= 11:59PM).
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be dis-
played:
20 NUMBERS MAXIMUM
The Phone Number screen is used to enter the Central Station phone number that the DACT will be
contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9 and A - C
where A = *, B = # and C = look for secondary dial tone for up to 2 seconds (then dial anyway).
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press
the right arrow key to move the cursor to the right one position. Enter the second digit and repeat
the process until all digits are entered. Press the Enter key to store the phone number in memory.
ACCOUNT CODE
Account Codes Screen
24 HOUR TEST TIME
24 Hour Test Time Screen
PHONE NUMBER
Phone Number Screen
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012