Master Programming Level
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms, or 3 to
view other events. Use the up and down arrow keys to scroll through all of the displayed events.

Erase History

The Erase History option allows a user to erase all events from the history file. This will provide a
clean slate in order to use the history file to track future events. Pressing 2 while viewing the His-
tory Screen will display the following screen:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. After
the History file has been erased, the display will return to the History Screen.
3.5.7 Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Refer to the sections titled "Walktest" on page 108 and"Walk-
test" on page 120 for additional information regarding the Walktest feature. Pressing 1 while view-
ing the Programming Screen #3 will cause the following Walktest options to be displayed:
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the follow-
ing screen will be displayed:
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
ERASE HISTORY
PROCEED ?
1=YES
Erase History Screen
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
UNIT IN WALKTEST
Walktest Active Screen