Seasonal Programs; Verify Ita-6 Operation (Manual Mode) - Airstream ITA-6 User Manual

Table of Contents

Advertisement

ITA-6

Seasonal Programs

All controller parameters can be set separately for winter and for summer
seasons. Select the proper season using internal switch #3 :
ON
=
OFF =

Verify ITA-6 Operation (Manual Mode)

Power the ITA-6 then select MANUAL MODE using the function
selector.
Use the adjustment knob to select the desired actuator status: se-
lect "OPn" to open, "CLo" to close or "OFF" to stop the actuator.
Select "AUt" to return to the automatic control mode.
VERIFY THE MOTOR'S OPERATION:
Manually open or close air inlet panels as explained above. These
panels should open when the "OPn" option is selected and should
close when the "CLo" option is selected. If they move the opposite
way, the motor operates in the wrong direction. Turn off the power
and reverse the wires connected to the actuator's open and close
terminals. Verify that the motor now operates in the right direction.
VERIFY LIMIT POSITIONS OF AIR INLET PANELS:
Select "CLo" to fully close the air inlet then place the limit switch
of the actuator at this position to prevent it from closing any fur-
ther; select "OPn" to fully open the air inlet then place a limit switch
at this position to prevent the actuator from opening any further.
14
ITA-6 rev.02
Winter
Summer
Make sure to select the right season
is selected before modifying a parameter.
ON
OFF


Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents