TC5-ITA

Calibration

The TC5-ITA adjusts the opening of air inlets according to the ventilation
stages provided by the environment controller. The calibration allows
TC5-ITA units to detect how many On/Off and variable stages the environ-
ment controller uses.
When the calibration is launched on the PRIMARY TC5-ITA unit, the envi-
ronment controller enters in test mode and starts simulating the room tem-
perature. The controller increases the simulated room temperature in or-
der to activate all of its ventilation stages. Each time a stage is activated,
a reference point is added to the TC5-ITA.
BEFORE CALIBRATING THE TC5-ITA:
It is preferable to calibrate the TC5-ITA while the room is empty
because the calibration will cause the activation of all fan stages.
Be sure that the circuit breakers at the service panel and all other
protection devices are in a position such that the fans can be acti-
vated.
Select the season you want to program with internal switch #3.