UC Open XP IO specifications
Power
Binary inputs
Universal inputs
Input resolution
Input pulse frequency
Binary outputs
Protection
Status indicators
Environmental operating
range
Storage temperature range
Physical
UC Open XP/UC Open XP IO
24 Vac ±10%, 50–60 Hz
13 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
IN 1 - 8 are binary only and support pulse counting up to 10 Hertz,
dry contact only.
IN 9 - 16 are universal inputs, jumper selectable between
thermistor/dry contact and 0-5 Vdc.
10 bit A/D
10 pulses per second max. Minimum pulse width (on or off time)
required for each pulse is 50 msec.
8 binary outputs, configured as dry contact, normally open, and
must be powered from a Class 2 power source.
Incoming power and network connections are protected by non-
replaceable internal solid-state polyswitches that reset themselves
when the condition that causes a fault returns to normal. The
power, network, input, and output connections are also protected
against voltage transient and surge events.
LED's indicate status of communications, running, errors, and
outputs
0 to 140° F (-18 to 60°C), 0 to 90% relative humidity, non-
condensing
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-
condensing
Rugged aluminum housing with removable screw terminals
5