UC Open XP installation
To wire the controller to the network
Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac or Hot.
1
Check the communications wiring for shorts and grounds.
2
Connect the communications wiring to the BACnet port's screw terminals labeled Net +, Net -, and
3
Shield.
NOTE Use the same polarity throughout the network segment.
Verify that the MSTP jumper is set to MSTP.
4
Set DIP switches 1 and 2 to the appropriate baud rate. See the MSTP baud diagram on the UC Open XP.
5
The default baud rate is 76.8 kbps.
NOTE Use the same baud rate for all controllers on the network segment.
Set DIP switches 3 and 4 for MSTP.
6
Verify the jumper is set on the right 2 pins.
7
Verify that the Communications Selection jumper is set to EIA-485.
8
Insert the power screw terminal connector into the UC Open XP's power terminals.
9
10 Verify communication with the network by viewing a module status report.