Appendix C: AHU CV Open input and output points list

AHU CV Open inputs and outputs on the UC Open XP IO

I/O
Type
Input
Terminal
BI-1
BI
1
BI-2
BI
3
BI-3
BI
5
BI-4
BI
7
BI-5
BI
9
BI-6
BI
11
BI-7
BI
13
BI-8
UI-9
AI
1
UI-10
UI-11
UI-12
UI-13
UI-14
UI-15
UI-16
BI
15
BO-1
BO
1
BO-2
BO
3
BO-3
BO
5
BO-4
BO
7
BO-5
BO
9
BO-6
BO
11
BO-7
BO
13
BO-8
BO
15
Legend
UI
- Universal Input
BI
- Binary Input
BO
- Binary Output
36
Gnd
Point Name/
Terminal
Function
2
Return/Exhaust Fan Status
4
High Duct RH
6
Fire Shutdown - FSD
8
Smoke Evacuation- EVAC
10
Smoke Pressurization - PRESS
12
Smoke Purge - PURGE
14
Enthaply Switch Input
2
Preheat Coil Temp
16
Filter Status 2
2
F&B 2 Pos Hot Water Valve
4
F&B 2 Pos Chilled Water Valve
6
DX Stage 4
8
DX Stage 5
10
DX Stage 6
12
Preheat 2 Pos Hot Water valve
14
Smoke Control K1
16
Smoke Control K2
Hardware/
Jumper
position of
Signal
terminals
Dry Contact
Middle
Dry Contact
Middle
Dry Contact
Middle
Dry Contact
Middle
Dry Contact
Middle
Dry Contact
Middle
Dry Contact
Middle
10K Thermistor
Middle
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A