NOTES
If using shielded wire, connect the shield to the GND terminal with the ground wire. Tape off the
shield wire at the sensor end.
Connect the shield wire to the GND terminal with the ground wire.
Use only UI-1 or UI-2 for pulse counter or timed local override.
For an internally-powered 4-20 mA sensor, wire the sensor's positive terminal to the + terminal on
the UC Open XP's Aux Power Out port. Wire the sensor's negative terminal to an input's + terminal.
UC Open XP/UC Open XP IO
15