Restore Factory Defaults; Serial Number - Carrier UC Open XP Installation And Startup Manual

Table of Contents

Advertisement

If Run LED shows...
2 flashes per second
5 flashes per second
5 flashes per second
7 flashes per second
14 flashes per second
On

Restore factory defaults

CAUTION!
reconfigure all custom settings. It is recommended to restore the factory defaults only under the guidance
of Carrier Control Systems Support.
To erase volatile memory data and restore factory default configuration settings:
Turn off the UC Open XP's power switch.
1
Put the Format jumper on.
2
Turn on the UC Open XP's power switch.
3
Remove the format jumper.
4

Serial number

If you need the UC Open XP's serial number when troubleshooting, the number is on:
a sticker on the back of the main controller board
a Module Status report (modstat) from your user interface
UC Open XP/UC Open XP IO
And Error LED shows...
On
On
Off
7 flashes per second,
alternating with Run LED
14 flashes per second,
alternating with Run LED
On
This erases all archived information and user-configuration settings. You will have to
Status is...
Exec halted after frequent system
errors or control programs halted
Exec start-up aborted, Boot is
running
Firmware transfer in progress,
Boot is running
Ten second recovery period after
brownout
Brownout
Failure. Try the following solutions:
Turn the UC Open XP off, then
on.
Download memory to the UC
Open XP.
Replace the UC Open XP.
27