UC Open XP IO Installation
UC Open XP IO Installation
To install the UC Open XP IO:
Mount the expander. (page 18)
1
Wire the expander for power. (page 19)
2
Address the expander. (page 19)
3
Wire inputs and outputs. (page 13, page 21)
4
To mount the UC Open XP IO
When you handle the UC Open XP IO:
• Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
• Do not touch components or leads.
• Handle the board by its edges.
• Isolate from high voltage or electrostatic discharge.
• Ensure that you are properly grounded.
Wiring restrictions for connecting the UC Open XP IO to the UC Open XP
Maximum length: 100 feet (30 meters)
○
22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
○
You can mount the UC Open XP IO in one of the following locations:
•
On top of a UC Open XP, using the two allen cap screws provided. Connect Gnd to Gnd, Xnet- to Xnet-,
Xnet+ to Xnet+.
18
UC Open XP/UC Open XP IO