No.
Error name
46
Motor parameters
47
Drive controller parameters
48
Type plate data
49
Power class restriction
53
Motor tipped
Tab. 12: Error detection
*
In exceptional cases, the error may be displayed erroneously when idling (very low motor current) with synchronous motors.
Set parameter 33.016 accordingly when the phases or motor connections are connected correctly.
**
Should the error occur again, depending on frequency, it can only be acknowledged after the following times:
1 -3
acknowledgements
permitted =
4 -5
acknowledgements
permitted =
> 5
acknowledgements
30 s waiting time
permitted =
The number of acknowledgements is deleted after 120 s without any errors!
Operating manual for DGM Modular | DOC02389740-0006 | 2021-07 | V1.70 EN
Description of error
Plausibility check for motor parameters failed
Plausibility check for drive controller
parameters failed
No motor data entered
Max. overload of the drive controller
exceeded for more than 60 sec.
Only for synchronous motors, field
orientation lost
1 s waiting time
5 s waiting time
Possible causes/remedy
Parameter set not OK
Parameter set not OK, motor type 33.001
and control method 34.010 not plausible.
Please enter the motor data according to
the type plate
Check application / reduce load / use
larger drive controller.
Load too high. Optimise controller
parameters.