Parameter
34.130
Relationship to
parameter:
This parameter can be used to adjust voltage output.
34.220
Relationship to
parameter:
The range calculated automatically (via motor identification) during which the pulse injection procedure runs is displayed
here.
34.225
Relationship to
parameter:
0 = disable, the motor cannot be run in the field weakening.
1 = enable, the motor can be placed in the field weakening until the
drive controller has reached its current limit or the maximum permissible
electromotive force.
34.226
Relationship to
parameter:
34.227
Only during start-up procedure: controlled.
Here the current which was stamped in the motor before starting the control can be adjusted. Value as % of nominal
motor current.
34.227
Relationship to
parameter:
34.226
Here the time during which the start up current 34.226 is stamped can be set.
76
Voltage control reserve
Transfer status:
2
Drive type
Injection RANGE
Transfer status:
1
Drive type
Field weakening
Transfer status:
2
Drive type
Starting current
Transfer status:
2
Drive type
Init time PMSM
Transfer status:
1
Drive type
Operating manual for DGM Modular | DOC02389740-0006 | 2021-07 | V1.70 EN
Unit:
min.:
0
Own value (to be entered!)
max.:
1
def.:
0.95
V/f
ASM
PMSM
x
x
Unit:
min.:
0
Own value (to be entered!)
max.:
1
def.:
0.02
V/f
ASM
PMSM
x
Unit: integer
min.:
0
Own value (to be entered!)
max.:
1
def.:
0
V/f
ASM
PMSM
Unit: %
min.:
5
Own value (to be entered!)
max.:
1000
def.:
25
V/f
ASM
PMSM
Unit: s
Own value (to be entered!)
min.:
0
max.:
100
def.:
0.25
V/f
ASM
PMSM
SRM
SRM
x
SRM
x
SRM
x
SRM
x