Connection For The I/O Module To Safety Switching Devices Or F I/O Modules; General Structure Of A Potential Group; Figure 11: Setting Up A Potential Group (Example); Table 22: Supply Or Filter Modules For Setting Up A Potential Group - WAGO 750-1515/040-000 Manual

8do 24vdc 0.5a 2-wire xtr 8-channel digital output; 24 v dc; 0.5 a; 2-wire connection, extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-1515/040-000 8DO 24VDC 0.5A 2-Wire XTR
Pos : 27.5 /Serie 750 (WAGO-I/O-SYST EM)/Eins atz in sicherheitsg erichteten Anwendung en/Allgemeiner Aufbau ei ner Potenti algruppe - r üc kwir kungsfr eie I/O-M odul e 750- xxxx/0040- xxxx @ 15\mod_1367561832729_21.doc x @ 118520 @ 23 @ 1
7.2
Connection for the I/O Module to Safety Switching
Devices or F I/O Modules
7.2.1

General Structure of a Potential Group

When using the interference-free I/O module 750-1515/040-000 in safety-related
applications, the I/O modules belonging to a safety switching device shall be
combined to form a potential group. The power supply of the potential group may
only be provided via the following supply or filter modules:

Table 22: Supply or Filter Modules for Setting up a Potential Group

Supply Terminal Blocks
Field-side power supply filter
Power supply filter
The potential group must be terminated by one of the listed supply or filter
modules or by the end module 750-600/040-000.
Pos : 27.6 /Serie 750 (WAGO-I/O-SYST EM)/Eins atz in sicherheitsg erichteten Anwendung en/Aufbau einer Potenti algruppe 0750xxxx-0040xxxx @ 15\mod_1367561860871_21.doc x @ 118524 @ @ 1

Figure 11: Setting up a Potential Group (Example)

Using in Safety Related Applications
750-602/040-000
750-612/040-000
750-613/040-000
750-624/040-001
750-626/040-000
39