Commissioning (basic settings)

10.
Commissioning (basic settings)
10.1.

Type of seating: set

Limit
Torque
Select main menu
Select parameter
CLOSE or OPEN
54
SA 07.2
SA 16.2/SAR 07.2
1.
Set selector switch to position 0 (OFF).
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is
maintained.
2.
Switch on the power supply.
Information: Observe heat-up time for ambient temperatures below 30 °C.
3.
Perform basic settings.
Valve damage due to incorrect setting!
The type of seating setting (limit or torque seating) must match the selection for
the valve.
Only change the setting with prior consent of the valve manufacturer.
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Default value: Limit
Setting values:
Seating in end positions via limit switching.
Seating in end positions via torque switching.
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: Press
Display indicates: End position CLOSED
4.
Use
Up ▲ Down ▼ to select:
▶ End position CLOSED
▶ End position OPEN
The black triangle ▶ indicates the current selection.
5.
Press
Ok.
Display indicates the current setting: Limit or Torque
The bottom row of the display indicates either:
-
Edit → continue with step 6
-
Save → continue with step 10
SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU
to parameter, or
and enter ID M0086 or M0087