Corrective action
Table 35:
Faults and Failure
Indication on display
Configuration error
Config. error REMOTE
Internal error
Torque fault CLOSE
Torque fault OPEN
Phase fault
Incorrect phase seq
Mains quality
Thermal fault
Fault no reaction
Poti Out of Range
1)
LPV not ready
Wrn input AIN 1
72
SA 07.2
SA 16.2/SAR 07.2
Description/cause
Collective signal 11:
Configuration error has occurred.
Collective signal 22:
Configuration error has occurred.
Collective signal 14:
Internal error has occurred.
Torque fault in direction CLOSE
Torque fault in direction OPEN
When connecting to a 3-ph AC system and with
internal 24 V DC supply of the electronics:
Phase 2 is missing.
When connecting to a 3-ph or 1-ph AC system
and with external 24 V DC supply of the elec-
tronics: One of the phases L1, L2 or L3 is
missing.
The phase conductors L1, L2 and L3 are connected
in the wrong sequence.
Only applicable if connected to a 3-ph AC system.
Due to insufficient mains quality, the controls cannot
detect the phase sequence (sequence of phase
conductors L1, L2 and L3) within the pre-set time
frame provided for monitoring.
Motor protection tripped
No actuator reaction to operation commands within
the set reaction time.
Potentiometer is outside the permissible range.
LPV: Lift Plug Valve function
The master actuator signals a fault
Loss of signal analogue input 1
SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU
Remedy
Press push button
Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Press push button
Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
AUMA service
Press push button
Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Perform one of the following measures:
Issue operation command in direction OPEN.
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
Execute reset command via fieldbus.
Perform one of the following measures:
Issue operation command in direction CLOSE.
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
Execute reset command via fieldbus.
Test/connect phases.
Correct the sequence of the phase conductors L1,
L2 and L3 by exchanging two phases.
Check mains voltage.
For 3-phase/1-phase AC current, the permiss-
ible variation of the mains voltage is ±10 %
(option ±30 %). The permissible variation of the
mains voltage is ±5 %
Check parameter Tripping time M0172, extend
time frame if required.
Cool down, wait.
If the fault indication display persists after cool-
ing down:
-
Set selector switch to position Local con-
trol (LOCAL) and reset fault indication via
push button RESET.
-
Execute reset command via fieldbus.
Check fuses.
Check movement at actuator.
Check device configuration:
Parameter Low limit Uspan M0832 must be less
than parameter Volt.level diff. potent. M0833.
Check wiring.