Electrical connection
6.2.2.

Cable connection

30
SA 07.2
SA 16.2/SAR 07.2
Table 20:
Terminal cross sections and terminal tightening torques
Designation
Power contacts
(U1, V1, W1, U2, V2, W2)
Protective earth connection
Control contacts
(1 to 50)
1.
Remove cable sheathing.
2.
Insert the wires into the cable glands.
3.
Fasten cable glands with the specified torque to ensure required enclosure
protection.
4.
Strip wires.
Controls approx. 6 mm, motor approx. 10 mm
5.
For flexible cables: Use wire end sleeves according to DIN 46228.
6.
Connect cables according to order-related wiring diagram.
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
Connect all protective earth conductors.
Connect PE connection to external protective earth conductor of connecting
cables.
Start running the device only after having connected the protective earth con-
ductor.
7.
Tighten PE conductors firmly to PE connection using ring lugs (flexible cables)
or loops (solid cables).
Figure 26: Protective earthing
[1]
Socket carrier
[2]
Screw
[3]
Washer
[4]
Lock washer
[5]
Protective earth with ring lugs/loops
[6]
Protective earthing, symbol:
8.
For shielded cables: Link the cable shield end via the cable gland to the housing
(earthing).
SAR 16.2 Control unit - electromechanical
Terminal cross sections
2
1.0
6 mm
(flexible)
2
1.5
10 mm
(solid)
2
1.0
6 mm
(flexible) with ring lugs
(PE)
2
1.5
10 mm
(solid) with loops
2
0.25
2.5 mm
(flexible)
2
0.34
2.5 mm
(solid)
AC 01.2 Intrusive Modbus RTU
Tightening torques
1.2
1.5 Nm
1.2
2.2 Nm
0.5
0.7 Nm