Connection Diagram For Alarm Outputs Am6 - E+E Elektronik EE310 Operation Manual

Humidity/temperature transmitter
Hide thumbs Also See for EE310:
Table of Contents

Advertisement

3.2.9

Connection diagram for alarm outputs AM6

NC
REL 2
C
NO
NC
REL 1
C
NO
Standard
Note:
½" Liquid-Tight Flexible Nonmetallic Conduit Type B (FNMC-B) is installed. Cable used for installation
shall be suitable flexible listed cord/cable in accordance with NEC. Local regulation for installation must
be observed.
Model
EE310 with option AM6
EE310 with option AM6
8 - 35 V DC
12 - 30 V AC
V
mA
V
mA
Model
EE310 with option AM6
18
NO
C
NC
NO
C
NC
Inverted
Relay 1:
Max. switch load: 250 Vac / 6 A and 28 Vdc / 6 A
Min. switch load: 12 Vacdc / 100 mA
Relay 2:
Max. switch load: 250 Vac / 6 A and 28 Vdc / 6 A
Min. switch load: 12 Vacdc / 100 mA
Wire size:
30-16AWG
Type:
CU
V+
1
Supply
GND
2
GND
3
Analogue outputs
OUT 1
4
OUT 2
5
GND RS485
6
Modbus RTU
RS485 A (=D+)
7
(galvanically isolated)
RS485 B (=D-)
8
Indoor use:
12 to 30Vac, 50/60Hz (Class 2 supply)
Outdoor use:
12 to 16Vac, 50/60Hz (Class 2 supply)
1
2
3
4
5
6
Supply Input
Voltage/Frequency
Terminal torque
USA:
6 Lb In.
CANADA:
0.7 Nm
Supply Input
Voltage/Frequency
8-35Vdc (LPS)
8-35Vdc (LPS)
Operating instructions for EE310 Humidity / Temperature Transmitter
Wire size:
18-16AWG
Type:
CU
Terminal torque
USA:
7 Lb In.
CANADA:
0.8 Nm
Terminals
C (5) -
NO (4)
C (5) -
NC (6)
C (2) -
NO (1)
C (2) -
NC (3)
Terminals
V+ (1) –
GND (2)