Modbus Map - E+E Elektronik EE310 Operation Manual

Humidity/temperature transmitter
Hide thumbs Also See for EE310:
Table of Contents

Advertisement

Menu
Modbus
settings*
Baudrate
Parity
Stop bits
Address
* Menu only available with connected Modbus RTU module during EE310 start-up.
Data transmission
Baud rate
Data bits
Parity
Stop bits
Slave address
The recommended setting for multiple devices in a Modbus RTU network is 9600 8 Even 1.
4.4

Modbus Map

Register
[DEC]
address [HEX]
Read registers: function code 0x03 / 0x04
31021
31003
31005
31105
31107
31131
31133
31113
31115
31121
31123
31109
31111
31125
31129
31127
31101
31103
31151
35001
Write registers: function code 0x06 for 16-bit and 0x10 (decimal: 16) for 32-bit
0001
5001
28
value
None
Odd
Even
value
value
Factory settings
9600
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800
8
8
EVEN
None, odd, even
1
1 or 2
231
1...247
Protocol
Measured value
3FC
Relative humidity
3EA
Temperature
3EC
Temperature
450
Dew point temperature
452
Dew point temperature
46A
Frost point / Dew point temperature
46C
Frost point / Dew point temperature
458
Absolute humidity
45A
Absolute humidity
460
Mixing ratio
462
Mixing ratio
454
Wet bulb temperature
456
Wet bulb temperature
464
Specific enthalpy
468
Specific enthalpy
466
Specific enthalpy
44C
Water vapour partial pressure
44E
Water vapour partial pressure
47E
Volume concentration
1388
Air pressure
0
Slave-ID
1388
Air pressure
Selectable values
Unit
Type
%
32-bit float
°C
32-bit float
°F
32-bit float
°C
32-bit float
°F
32-bit float
°C
32-bit float
°F
32-bit float
g/m
32-bit float
3
gr/ft
32-bit float
3
g/kg
32-bit float
gr/lb
32-bit float
°C
32-bit float
°F
32-bit float
kJ/kg
32-bit float
BTU/lb
32-bit float
ft lbf/lb
32-bit float
mbar
32-bit float
psi
32-bit float
ppm
32-bit float
mbar
32-bit float
/
16-bit integer
mbar
32-bit float