Humidity and temperature transmitter for demanding climate control applications
Hide thumbs Also See for EE210:

Advertisement

CONNECTION DIAGRAM

EE210-HT6
ONLY FOR REMOTE PROBE!
EE210-HT3
EE210-HT2/3/5
ONLY FOR REMOTE PROBE!
EE210-HTx3
confi guration connector
EE210P (type C)
The EE210P remote probe for EE210-HTxxPC shall be ordered and it is supplied as separate item. EE210P is to be connected to the
EE210 by the user.
Install first the cable gland (included in EE210 scope of supply) onto the EE210 enclosure.
Before connecting the probe, disconnect the EE210 power supply.
Insert the EE210P cable through the cable gland and connect it to the screw terminals according to the connection diagram
below.
Please note:
EE210P is an intelligent probe with digital output and as such it is interchangeable. In case the probe or its cable gets destroyed or if a
longer cable is needed, please order a replacement probe according to EE210 data sheet. The replacement probe shall be installed as
described above.
Important:
Make sure that the cable glands are closed tightly for both EE210P probe cable and for the power supply and outputs cable. This is
necessary for assuring the protection class (IP class) of the enclosure according to EE210 specifi cation, as well as for stress relief at
the screw terminals on the EE210 board.
EE210-HT6
20...30 V DC R
<500 Ohm
L
11...30 V DC R
<50 Ohm
L
Output: 4-20 mA
Important: The EE210-HT6 (4...20 mA, two-wire) with display operates correctly only if both outputs are connected.
EE210-HT2/3/5
15...35 V DC
24 V AC ±20 %
Output: 0-5 V
0-10 V
0-20 mA
Selection ouput signal U / I
EE210-HTx3
15...35 V DC
24 V AC ±20 %
Output:
Modbus RTU or
BACnet MS/TP
Bus termination resistor 120 Ω (jumper)
OUT1
OUT2
OUT1
V
V
OUT2
mA
mA