Download Print this page
E+E Elektronik EE150 User Manual

E+E Elektronik EE150 User Manual

Humidity and temperature transmitter for hvac applications

Advertisement

Quick Links

USER'S GUIDE
EE150 - Humidity and Temperature Transmitter for HVAC applications

SCOPE OF SUPPLY

EE150 transmitter, type number according to order (for ordering guide see data sheet at www.epluse.com/EE150)
Cable gland M16 x 1.5
Mounting flange, PC, Ø 6.0mm
Test report according to DIN EN 10204 – 2.2
CAUtiOn
For accurate measurement it is essential that the temperature of the probe and mainly of the sensing head is same as the
temperature of the air to measure.
Avoid mounting the EE150 transmitter in a way which creates temperature gradients along the probe. If possible, EE150 shall
be installed with the entire probe inside the duct. For installation with mounting flange, in case of different temperature inside
and outside the duct, the probe part outside the duct shall be thermally isolated.
The device and mainly the sensing head shall not be exposed to extreme mechanical stress.
Do not attempt to remove the filer cap, which is fixed. Avoid touching the sensing head at all times.
The stainless steel probe is ESD sensitive and shall be handled as such. Do not connect it to the ground potential.

COnnECtiOn diAgrAm

EE150-HT6xxx
setup and adjustment interface (with EE-PCA)
EE150-HT3xxx
setup and adjustment interface (with EE-PCA)
dimEnSiOnS / mOUnting
Dimensions: mm (inch)
(class III)
(class III)
ø 4 (ø 0.16)
CABLE GLAND M16x1.5
T-passive connection
for HT3xxx/HT6xxx
5
6
drilled hole for
mounting: ø>9 (ø>0.35)
ø 5 (ø 0.2)

Advertisement

loading

Summary of Contents for E+E Elektronik EE150

  • Page 1: Scope Of Supply

    USER‘S GUIDE EE150 - Humidity and Temperature Transmitter for HVAC applications SCOPE OF SUPPLY • EE150 transmitter, type number according to order (for ordering guide see data sheet at www.epluse.com/EE150) • Cable gland M16 x 1.5 • Mounting flange, PC, Ø 6.0mm • Test report according to DIN EN 10204 – 2.2 CAUtiOn • For accurate measurement it is essential that the temperature of the probe and mainly of the sensing head is same as the temperature of the air to measure. • Avoid mounting the EE150 transmitter in a way which creates temperature gradients along the probe. If possible, EE150 shall be installed with the entire probe inside the duct. For installation with mounting flange, in case of different temperature inside and outside the duct, the probe part outside the duct shall be thermally isolated. • The device and mainly the sensing head shall not be exposed to extreme mechanical stress. • Do not attempt to remove the filer cap, which is fixed. Avoid touching the sensing head at all times. • The stainless steel probe is ESD sensitive and shall be handled as such. Do not connect it to the ground potential. COnnECtiOn diAgrAm EE150-HT6xxx (class III)
  • Page 2: Technical Data

    (23...131°F) Storage conditions -25...60°C 20...80% RH (-13...140°F) SEtUP And AdJUStmEnt The EE150 is ready to use and does not require any configuration by the user. The factory setup of EE150 corresponds to the type num- ber ordered. For ordering guide please see data sheet at www.epluse.com/EE150. If needed, the user can change the factory setup by using the optional E+E Product Configuration Adapter (EE-PCA) and the E+E Product Configuration Software (EE-PCS). With these one can set the output scaling, and perform one or two point adjustment for humidity and temperature.