6.1

Connection Diagram

EE220- x1x
- x3x
power supply
for 0 - 1 V:
10 - 35 V DC
9 - 29 V AC
for 0 - 10 V: 15 - 35 V DC
15 - 29 V AC
7

User Interface

4-20 mA version
1. JUMPER:

2. DISPLAY:

3. CALIB LED:
4. S1 Functions
5. S2 Functions
S1+S2 Function:
7.1
Display
8
EE220- x6x
power supply
20...35 V DC; R
11...35 V DC; R
• selection of output signals and of calibration mode
voltage output
selection of output
• socket for optional display
• continuously on indicates adjustment mode
• 1 flash confirms reset to factory calibration
• 1-point RH or T adjustment
(RH > 50%RH; T within the upper half of the T scale)
• 2-point RH or T adjustment (high calibration point)
• save adjustment data
• 1-point RH or T adjustment
(RH < 50%RH; T within the lower half of the T scale)
• 2-point RH or T adjustment (low calibration point)
• exit the adjustment mode without saving the data
• reset to factory calibration
1. CAL
1. CAL:
2. °C / °F
2. °C / °F:
3. %RH
3. % RH:
Operating instructions for EE220 humidity / temperature transmitter
<500 Ω
L
< 50 Ω
L
4. Push-Button S1
5. Push-
4-20 mA output
Calib
T
RH
• indicates adjustment mode
• T measuring unit
• RH measuring unit
option C03
4
3
5
1
2
1... brown .... T
2... white ..... RH
3... blue ....... NC
4... black ..... GND
5... grey ...... V+
Jumper
1.
Display
2.
3. Calib Led
Button S2