CoNNECtioN diAGRAm

EE820 with M12 plug
1)
1) Mating M12x1 connector for self assembly is included in the scope of supply
2) Very important: for failure-free operation and performance according to the
specs the supply GND and the measurement GND must be
wired separately.

tECHNiCAL dAtA

(Modification rights reserved)
Measured values
Measuring principle
Measurement range
Accuracy at 25 °C and 1013 mbar
(77 °F...14,7 psi)
Response time τ
63
Temperature dependency
Sample rate
Output
0...2000 / 5000 / 10000 ppm
General
Supply voltage
Current consumption
Current peak
Warm up time
1)
Housing material
Protection class
Electrical connection
Electromagnetic compatibility
Working conditions
Storage conditions
1) for performance according to specification
EE820 with cable gland
dual wavelength non-dispersive infrared technology (NDIR)
0...2000 / 5000 / 10000 ppm
0...2000 ppm:
< ± (50 ppm +2 % of measured value)
0...5000 ppm:
< ± (50 ppm +3 % of measured value)
0...10000 ppm:
< ± (100 ppm +5 % of measured value)
standard: typ. 300 s
fast:
typ. 140 s (with a forced air circulation module)
typ. ± (1 + CO
concentration [ppm] / 1000) ppm/°C (-20...45 °C)
2
approx. 15 s
0 - 5 / 0 - 10 V
-1mA < I
4 - 20 mA
R
< 500 Ohm
L
24 V AC
±20%
15 - 35 V DC
standard:
typ. 15 mA + output current
fast:
typ. 60 mA + output current
max. 350 mA for 0.3 s
< 5 min
Polycarbonate, UL94V-0 approved
IP54
Screw terminals 2.5 mm² or M12 plug
EN61326-1
EN61326-2-3
FCC Part 15
ICES-003 ClassB
-20...60 °C
0...100 % RH (non-condensing)
(-4...140°F)
-20...60 °C
0...95 % RH (non-condensing)
(-4...140°F)
< 1 mA
L
Industrial Environment
(-4...113 °F)