Reserved
002Bh
002Ch
RELAY
STATUS
ECI STATUS 002Dh
SYSTEM
002Eh
STATUS
Mrst
002Fh
Reserved
0030h
Reserved
0031h
0032h
Reserved
Reserved
0033h
Programming Level
[Input Group]
Name
Address
Vunit
0034h
pTsec*
0035h
cTsec*
0036h
Wunit
0037h
0038h
Reserved
pVzro
0039h
pVspn
003Ah
ZSclr
003Bh
dsply
003Ch
lOcut
003Dh
avg
003Eh
Dfilt
003Fh
0040h
Reserved
Pcode
0041h
One Word
0~1
RELAY STATUS
bit0~bit3:relay1~relay4;
0=Relay off 1=Relay on
0~1
ECI STATUS
bit0~bit2:ECI.1~ECI.3; 0=untriged 1:triged
0~1
SYSTEM STATUS
bit0=1 EEP fail;
bit1=1 Input calibration fail;
bit2=1 Input calibration NG;
bit3=1 Analogue Output calibration fail;
bit4=1 Analogue Output calibration NG
0~1
Reset Maximum & Minimum Value storage
0:No(
Range
0~1
Unit for Primary Voltage of PT
0: V (
500~5000
Secondary Voltage of PT
1000~9999
Secondary Current of CT
0~6
Unit and Resolution of Power
0: 1W(
2: 0.1KW(
4: 0.01MW( )01mW)
6: 0~1MW(
0~99999
POWER(WATT) Zero
0~99999
POWER(WATT) Span
0~3
to clear of POWER(WATT).ZRO and
POWER(WATT).SPn
0: None( none)
1:POWER(WATT).ZRO(pVzro)
2:POWER(WATT).SPN(pVzro)
3:Both( both)
0~3
Display Mode for down screen
0: POWER(WATT)(
1: Minimum Hold(miNhd)
2: Maximum Hold(maXhd)
3: RS485(rs485)
0~10000
Low Cut of Power(Watt)
1~99
Average display for Power(Watt)
0~99
Digital Filter for Power(Watt)
0000~9999
Pass Code
MW-5 Operating Manual 2012-07-19
no) 1:Yes(
yes)
Explain
v)
1: kV (
kv)
*(High word)
*(High word)
1W)
1: 0.01KW( )01kW)
)1kW)
3: 1KW(
5: 0.1MW(
1mW)
pv)
00h
00h
00h
Initial
Write/Read Note
5000
5000
1
1kW)
)1mW)
0
0
00h
00h
0
5
0
1000
R
R/W
R
R
R/W
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
33 / 36