ADTEK MW-5 Operating Manual page 28

Table of Contents

Advertisement

aOhs
19999
19999
15000
aOzro
00000
0
`7233
aOspn
00000
0
32767
ZSclr
none
none
both
aOlmt
11)00
11)00
10)00
26 / 36
aOhs(Ao.HS): the High point is
relative to Analogue Output high;
To set the higher display value to
versus output range high(as like as
20mA in A4-20)
Ex. Ourput range set to be A4-20
(4~20mA) is relative to display 0~199.99.
User can set the [aOhs] (Ao.HS) to be
15)00. At meantime, the output signal
will be 20mA when the present value(PV)
is 150.00.
aOzro(Ao.Zro): Fine Zero
Adjustment for Analog Low Output;
Users can get Fine zero Adjustment for
analogue output by front key. Please
connect standard meter to the terminal
of analogue output. To press the front
key(up or down key) to adjust and
check the output of meter.
aOspn(Ao.SPn): Fine Span
Adjustment for Analog high Output;
Users can get Fine span Adjustment for
analogue output by front key of the
meter as like as [aOzro] (Ao.Zro).
ZSclr(Z.S.CLr): Clear the Fine Zero /
Span Adjustment for Analog Output
aOlmt(Ao.LMt): Analog Output High
Limit
Set Scaling: [ lOsc]:
Output: [ aOls]:
5)00 (Display value Low),
SCALE
[ aOhs]: 15)00 (Display value High);
[ hIsc]
[ aOlmt]:
8)00%( of Output Range)
19(99
[ aOhs]
Ao.LMt: 80.00%
15)00
10)00
[ aOls]
5)00
[ lOsc]
)00
0.00%
50.00%
MW-5 Operating Manual 2012-07-19
Settable range: 0~99999
Shift
Settable range: -38011~27524
Shift
Settable range: -38011~27524
Shift
Programmable:
none(None): Do not clear
aOzro(Ao.Zro): Clear low adjust
aOspn(Ao.SPn): Clear high adjust
both(both): Clear low & high adjust
&
Settable range:
-0.00~ 110.00% of FS
)00, [ hIsc]: 19(99;
Shift
OUTPUT
100.00%
80.00%
[ aOlmt]
Up
Down
Enter
Up
Down
Enter
Up
Down
Enter
Selection
Enter
Up
Down
Enter