Wiring For Start/Stop - Danfoss FC 102 Operating Manual

Vlt hvac drive, 355–800 kw, enclosure size e
Hide thumbs Also See for FC 102:
Table of Contents

Advertisement

Wiring Configuration Exampl...
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
29
D IN
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
7
7
COM
39
Table 7.4 Speed Up/Speed Down
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 7.1 Speed Up/Speed Down
56
VLT® HVAC Drive FC 102
Parameters
Function
Setting
Parameter 5-10 Termin
[8] Start*
al 18 Digital Input
Parameter 5-12 Termin
[19]
al 27 Digital Input
Freeze
Referenc
e
Parameter 5-13 Termin
[21]
al 29 Digital Input
Speed
Up
Parameter 5-14 Termin
[22]
al 32 Digital Input
Speed
Down
* = Default value
Notes/comments:
Danfoss A/S © 01/2017 All rights reserved.

7.2 Wiring for Start/Stop

FC
+24 V
12
+24 V
13
18
D IN
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 7.5 Start/Stop Command with Safe Torque Off Option
Speed
Start/Stop (18)
Illustration 7.2 Start/Stop Command with Safe Torque Off
Parameters
Function
Setting
Parameter 5-10
[8] Start*
Terminal 18
Digital Input
Parameter 5-12
[0] No
Terminal 27
operation
Digital Input
Parameter 5-19
[1] Safe Stop
Terminal 37 Safe
Alarm
Stop
* = Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.